7.3.6.4 IODDs
GET/iodds
Readout of all IODDs located on the device.
Query parame‐
ters
Type Description
vendorId
Integer Output of the IODDs available on the device with the
specified vendor ID.
deviceId
Integer Output of the IODDs available on the device with the
specified device ID.
revision
Enum
[“1.0”/ “1.1”]
Output of the IODDs available on the device with the
specified revision.
Namespace example with query parameters
http://192.168.2.1/iolink/v1/iodds?vendorId=26&deviceId=8389227
http://192.168.2.1/iolink/v1/iodds?revision=1.1
Sample response:
[
{
"vendorId": 26,
"deviceId": 8389010,
"version": "V1.04",
"releaseDate": "2018-07-17",
"iolinkRevision": "1.1"
},
{
"vendorId": 26,
"deviceId": 8389238,
"version": "V0.1",
"releaseDate": "2020-11-19",
"iolinkRevision": "1.1"
},
]
GET/iodds/file
Read out the IODD file specified by the query parameters. Vendor and Device ID are
required here.
Namespace example with query parameters:
http://192.168.2.1/iolink/v1/iodds/file?vendorId=26&devi-
ceId=8389010
Sample response:
SIG200 CONFIGURATION 7
8024482.1FJ7 /2022-05-31 | SICK O P E R A T I N G I N S T R U C T I O N | Sensor Integration Gateway - SIG200
43