Installation checks and 
functional tests
Removal from cell in outdoor non-walk-
in enclosures or for indoor switchgear 
installed on a raised pad
Removal of the circuit breaker from a non-
walk-in outdoor-switchgear assembly is 
similar to removal of a circuit breaker at 
floor level with several additional steps.
Figure 3 shows the two extension rails 
inserted into the fixed rails within the cell. 
The rails engage locking pins in the fixed 
rails to secure them in position. The 
procedure for removal of a circuit breaker 
not located at floor level is:
1.    Close the circuit-breaker compartment 
door and secure all latches.
2.    Insert the racking crank onto the 
racking screw on the front of the 
circuit-breaker cell, and push in (refer 
to "Racking crank engagement 
procedure" on page 11). This action 
operates the racking-interlock latch.
3.    Rotate the racking crank 
counterclockwise until the circuit 
breaker is in the DISCONNECT position.
4.    Open the circuit-breaker compartment 
door and insert the two extension rails 
into the fixed rails. Be sure the 
extension rails are properly secured in 
place.
Heavy weight.
Can result in death, serious injury or property damage.
Observe all handling instructions in this instruction manual to 
prevent tipping or dropping of equipment.
Removal from cell in indoor switchgear 
if not on raised pad and Shelter-Clad 
outdoor switchgear
After performing the spring discharge 
check (with control power de-energized), 
remove the circuit breaker from its 
switchgear cubicle.
1.    Insert the racking crank on the racking 
screw on the front of the circuit 
breaker cell, and push in (refer to 
"Racking crank engagement procedure" 
on page 11). This action operates the 
racking-interlock latch. Figure 2 shows 
circuit breaker racking.
2.    Rotate the racking crank 
counterclockwise until the circuit 
breaker is in the DISCONNECT position, 
as indicated on the racking 
mechanism.
3.    Move the circuit breaker release latch 
(on the floor of the cell near the right 
side of the circuit breaker) to the left 
and pull the circuit breaker out from 
the DISCONNECT position. The circuit 
breaker can now be removed from the 
cubicle.
4.    The circuit breaker is now free to be 
rolled out onto the floor using the 
handles on the front. The wheels of the 
circuit breaker are at floor level (unless 
the switchgear is installed on a raised 
pad), and one person can normally 
handle the unit.
10