Transport, storage and packing
16 9229 9992 176 0D
2013-07-08
Reusing the transport unit
Reusing the transport unit To transport the vacuum circuit-breaker again, the pallet with carton or the wooden
case with the most components can be reused.
Do not reuse severed tensioning straps or plastic wrap.
Pack the vacuum circuit-breaker in reverse order:
• Attach the vacuum circuit-breaker safely to the pallet using the appropriate
tools.
• Cover with foil and seal with adhesive tape.
• Attach accessories pack.
• Attach carton securely to the pallet base.
• Screw the wooden case back together.
• Before returning to the factory, ask the responsible Siemens representative for a
returned goods number (see also “Service” on page 59).
• When returning a vacuum circuit-breaker, always indicate the type and serial
number (see “Rating plate” on page 34).
Storage
Note
Store the vacuum circuit-breaker in the following condition:
• OPEN switching position
• Closing spring discharged
Note
Risk of corrosion damage if stored improperly!
If the storage conditions listed below are met, the vacuum circuit-breaker can be
stored for up to a year in its transport unit.
If the storage conditions are not met, the vacuum circuit-breaker cannot be stored
in the transport unit any longer than 6 months.
If storage of longer than one year is planned, unpack the vacuum circuit-breaker
from the transport unit. Further storage may necessitate fresh corrosion
protection, and it must be ensured that the vacuum circuit-breaker cannot be
damaged.
Storage room Transport unit Storage time Temperature range Comments Number of
units per
stack
Enclosed, dry, well
ventilated and as
free from dust as
possible, with a
relative humidity of
less than 60 %.
unopened max. 6 months -40 °C to +55 °C — max. 4
unopened max. 1 year -5 °C to +40 °C — max. 4
open over 1 year -5 °C to +40 °C
if necessary,
with new
corrosion
protection
—