Configuration and operation
6.11 SNMP agent
CP 343-1 Lean
Equipment Manual, 01/2023, C79000−G8976−C198−09
53
Exceptions / restrictions:
Write access is permitted only for the following MIB objects of the system group:
sysContact
sysLocation
sysName
A set sysName is sent as the host name using DHCP option 12 to the DHCP server to
register with a DNS server.
For all other MIB objects / MIB object groups, only read access is possible for security
reasons.
Traps are not supported by the CP.
"Interfaces" MIB group
This group returns status information about the CP interfaces. The MIB objects of the ifTable
provide the status information of the interfaces. The "ifIndex" object identifier is assigned to
the CP interfaces as follows:
Table 6- 1 Assignment of ifIndex
ifIndex
Type of interface
1-2
Port 1-2
3
Internal CP interface
Access permissions using community name
The CP uses the following community names to control the access rights in the SNMP agent:
Table 6- 2 Access rights in the SNMP agent
Type of access
Community name
*)
Read access
public
Read and write access
private
*) Note the use of lowercase letters!

Table of Contents

Other manuals for Siemens 6ES7 305-1BA80-0AA0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 6ES7 305-1BA80-0AA0 and is the answer not in the manual?

Siemens 6ES7 305-1BA80-0AA0 Specifications

General IconGeneral
BrandSiemens
Model6ES7 305-1BA80-0AA0
CategoryController
LanguageEnglish

Related product manuals