Analog input module SM 331; AI 6 x TC Isolated (6ES7331‑7PE10‑0AB0)
24 A5E02398493-02, 11/2008
Instructions
The field "Instructions" provides information as to what you have to do yourself during the current calibration step. You have
to perform these actions, and then confirm them using the button "Continue". The module then carries out the actions
required for the current calibration step, and if this step was processed without fault, moves to the next calibration step.
If during user calibration you do not want to record one or several calibration values anew, you can acknowledge the current
calibration step with the button "Skip this step" instead of the button "Continue". In this case, the factory calibration value will
be used for the ‘skipped’ calibration step (refer to the field "Comment").
The last calibration step displays the calibration values determined in the course of the calibration.
23
4
1
① New calibration values
② Cancels the entire calibration function
③ Cancels the current calibration and returns to the basic screen
④ Confirms the ascertained calibration values, stores the calibration values, and returns to the basic screen
Figure User Calibration Values
With the button "Continue", these calibration values can now be accepted as new calibration values. The calibration values
are stored retentively, and the calibration of the channel is exited
If you do not want to use the displayed calibration values, you can return to the basic screen using the button "Restart" and
restart the calibration, or exit the entire calibration functionality using the button "Cancel".