Current-Balance Supervision
Setting Values
Release threshold I
rated
= 1 A 0.030 A to 35.000 A Increments of 0.001 A
I
rated
= 5 A 0.15 A to 175.00 A Increments of 0.01 A
Threshold min/max 0.10 to 0.95 Increments of 0.01
Delay failure indication 0.00 s to 100.00 s Increments of 0.01 s
Dropout Ratio
Overcurrent dropout ratio Approx. 0.97
Undercurrent dropout ratio Approx. 1.05
Times
Tripping time Approx. 500 ms
Dropout time Approx. 500 ms
11.38
Technical Data
11.38 Current-Balance Supervision
1206 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-A, Edition 05.2018