Trip-Circuit Supervision
Setting Values
Number of monitored circuits per circuit-breaker function group 1 to 3
Operating mode per circuit With 1 binary input
With 2 binary inputs
Pickup and dropout time About 1 s to 2 s
Adjustable indication delay with 1 binary input 1.00 s to 600.00 s Increments of 0.01 s
Adjustable indication delay with 2 binary inputs 1.00 s to 600.00 s Increments of 0.01 s
11.44
Technical Data
11.44 Trip-Circuit Supervision
1212 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-A, Edition 05.2018