Siemens 7MF0330 - 8.2 Measuring accuracy of SITRANS P320

Siemens 7MF0330
106 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Level measuring limits
Lower measuring limit
Measuring cell with silicone oil
filling
-100% of max. measuring range or 30 mbar a/3 kPa a/0.44 psi a depending
on the mounting flange
Measuring cell with inert oil -100% of max. measuring range or 30 mbar a/3 kPa a/0.44 psi a depending
on the mounting flange
Measuring cell with FDA-com‐
pliant oil
-100% of maximum measuring range or 100 mbar a /10 kPa a /1.45 psi a
Upper measuring limit 100% of max. range
Lower range value Between the measuring limits (continuously adjustable)
8.2 Measuring accuracy of SITRANS P320
8.2.1 Reference conditions
According to EN 60770-1/IEC 61298-1
Rising characteristic curve
Lower range value 0 bar/kPa/psi
Seal diaphragm stainless steel
Measuring cell with silicone oil filling
Room temperature 25 °C (77 °F)
8.2.2 Effect of auxiliary power supply
0.005% per 1 V (in percent per change in voltage)
8.2.3 Gauge pressure
Conformity error at limit point setting, including hysteresis and repeatability - gauge pressure
Measuring span ratio r (spread, Turn-Down) r = max. measuring span/set measuring span and nominal
measuring range
Linear characteristic curve
r ≤ 1.25 1.25 < r ≤ 30
250 mbar/25 kPa/3.6 psi ≤ 0.075% ≤ (0.008 • r + 0.055)%
Linear characteristic curve
r ≤ 5 5 < r ≤ 100
Technical data
8.2 Measuring accuracy of SITRANS P320
SITRANS P320/P420 with 4 to 20 mA/HART
Compact Operating Instructions, 09/2018, A5E38874562-AB 69