$SSHQGL[6$
9
&* &
¿©©©©§©©©©©©©©©©©©©§©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©§©©§©©§©§©©©¤
FNo.Abbreviation Meaning OpFtEIOT
¨©©©©ª©©©©©©©©©©©©©ª©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©ª©©ª©©ª©ª©©©
4282S-O-F Flt. L1Switch-onto-fault: Fault detection L1 COT
4283S-O-F Flt. L2Switch-onto-fault: Fault detection L2 COT
4284S-O-F Flt. L3Switch-onto-fault: Fault detection L3 COT
4295S-O-F Trip 3pSwitch-onto-fault: Trip 3pole COT
4301>U> Prot. on >Switch on overvoltage protection U> IOT
4302>U> Prot. off>Switch off overvoltage protection U >IOT
4304>U>>Prot. on >Switch on highset protection U>> IOT
4305>U>>Prot. off>Switch off highset protection U>> IOT
4306>U> Block >Block overvoltage protection U> IOT
4307>U>> Block >Block highset overvoltage protectionIOT
4323U>/U>> activeOvervoltage protection active OT
4325U> off Overvoltage stage U> is switched off CG OT
4326U> blocked Overvoltage stage U> is blocked CG OT
4328U>> off Overvoltage highset U>> is switched offCG OT
4329U>> blocked Overvoltage highset U>> is blocked CG OT
4331U> Detection Overvoltage detection : Stage U> CG OT
4332U>> DetectionOvervoltage detection : Stage U>> CG OT
4335U> Trip Overvoltage trip : Stage U> COT
4336U>> Trip Overvoltage trip : Stage U>> COT
4339U> Intertrip Overvoltage stage U> intertrip send COT
4340U>> IntertripOvervoltage highset U>> intertrip send COT
4403>Ext.Trip blk>Block external trip function CG IOT
4412>Ext.Trip L1 >External trip L1 via binary input C IOT
4413>Ext.Trip L2 >External trip L2 via binary input C IOT
4414>Ext.Trip L3 >External trip L3 via binary input C IOT
4416>Ext.Trp.woAR>External 3pole trip without AR CG IOT
4431Ext.Gen. TripExt. trip via binary input: Trip OT
4432Ext.Trip 1pL1Ext. trip via binary input: 1pole L1 COT
4433Ext.Trip 1pL2Ext. trip via binary input: 1pole L2 COT
4434Ext.Trip 1pL3Ext. trip via binary input: 1pole L3 COT
4435Ext.Trip 3p Ext. trip via binary input: 3pole COT
4436Ext.Trip woARExt. trip via binary input: Without AR COT
6206>User T1Start>Start of user defined timer T1 CGCG IOT
6207>User T1Reset>Reset of user defined timer T1 C C IOT
6208>User T2Start>Start of user defined timer T2 CGCG IOT
6209>User T2Reset>Reset of user defined timer T2 C C IOT
6254User output 1Output signal of user defined timer T1 CGCOT
6255User output 2Output signal of user defined timer T2 CGCOT
¥©©©©¦©©©©©©©©©©©©©¦©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©¦©©¦©©¦©¦©©©¾