9

&*&
3114 MAN.CLOSE Mode of operation with manual close (M/C)
OFF [ ] off
F/D UNDELAYED [ ] F/D undelayed
F/D DIRECTIONAL [ ] F/D directional
3115 T-DIR. RAR Delay for RAR (3113) and MC w/ F/D dir (3114)
min. 0.00 s
max. 32.00/Ñ ©©©©
3117 DIS BL E/F Dist.prot.pick-up: Earth fault prot. BLOCKED
YES [ ] yes
NO []no
3118 E/F BLO/1p AR 1p. dead-time: Earth fault prot. BLOCKED
YES [ ] yes
NO []no
3125 TRIP1P E/F Trip single-pole with earth flt.prot. ENABLED
YES [ ] yes
NO []no
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
3200 EARTHFAULT DIREC.COMPARISON
3201 E/F COMPAR Earth fault directional comparison is
ON []on
OFF [ ] off
3202 T-DELAY Delay-time for transmission and trip
min. 0,00 s
max. 32.00/Ñ ©©©©
3203 T-TRANSBLO Transient blocking time after external fault
min. 0.01 s
max. 32.00 ©©©©
3204 T-WAIT Waiting time for trans.block. (missing recept)
min. 0.01 s
max. 32.00/Ñ ©©©©
3206 TW REVERSE Waiting time for trans.block. (reverse faults)
min. 0.01 s
max. 32.00/Ñ ©©©©
3210 E/F ECHO Echo function for weak infeed
ON []on
OFF [ ] off
3211 T-ECHO-DEL Echo delay time
min. 0.01 s
max. 32.00/Ñ ©©©©
3212 T-ECHO-IMP Duration of echo impulse
min. 0.02 s
max. 32.00 ©©©©
3213 T-ECHO-BLO Echo blocking time
min. 0.01 s
max. 32.00 ©©©©