$SSHQGL[6$
9

&*&
3426 RAR T-1POL RAR 1pole dead time
min. 0.01 s
max. 320.00 ©©©©
3427 RAR T1POL2 RAR accelerated 1pole dead time (U0 dependent)
min. 0.01 s
max. 320.00 ©©©©
3428 EV.F.RECOG Evolving fault recognition with 1pole AR
WITH FAULT DETEC [ ] With fault detection
WITH TRIP COMM. [ ] With trip command
3429 EV.F.BLOCK Blocking with evolving faults
ALWAYS [ ] Always
NEVER [ ] Never
>T-DISCR. [ ] >T-discrimination
3430 T-DISCRIM Discrimination time for evolving faults
min. 0.01 s
max. 320.00 ©©©©
3431 AR TRIP 3P 3p trip when AR is blocked during 1p dead time
YES [ ] yes
NO []no
3442 DAR PROG. Delayed auto-reclose program
NO DAR [ ] No DAR
DAR WITHOUT RAR [ ] DAR without RAR
DAR AFTER RAR [ ] DAR only after RAR
3443 DAR No.1PH Number of DAR shots after 1 pole initiation
min. 0
max. 9 ©©©©
3444 DAR No.3PH Number of DAR shots after 3 pole initiation
min. 0
max. 9 ©©©©
3445 DAR T-ACT. Delayed auto-reclose action time
min. 0.01 s
max. 320.00/Ñ ©©©©
3446 DAR T3POL1 DAR 3pole dead time for 1st shot
min. 0.01 s
max. 1800.00 ©©©©
3447 DAR T3POL2 DAR 3pole dead time for 2nd shot
min. 0.01 s
max. 1800.00 ©©©©
3448 DAR T3POL3 DAR 3pole dead time for 3rd and further shots
min. 0.01 s
max. 1800.00 ©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
3500 CHECK SYNCHRONISM
3501 SYNC-CHECK Synchro-check function
ON []on
OFF [ ] off