3527 MC U1<U2> Dead line/live bus check before MC (U1</U2>)
NO []no
YES [ ] yes
3528 MC U1<U2< Dead line/dead bus check before MC (U1</U2<)
NO []no
YES [ ] yes
3529 MC O/RIDE Override of any check before MC
NO []no
YES [ ] yes
3530 T-SYN.SUPV Synchro-check supervision time
min. 0.01 s
max. 320.00 ©©©©
3531 T IN-SYNC Synchronism criteria maintained timer
min. 0.00 s
max. 32.00 ©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
3600 BACK-UP OVERCURRENT PROT
3601 BACK O/C P State of back-up overcurrent prot.: phase
ON []on
OFF [ ] off
3602 I>> Highset phase overcurrent threshold (DT) I>>
min. 0.10 I/In
max. 9.99 I/In
max. 15.00 ©©©©
3603 T-I>> Delay time for I>> TI>>
min. 0.00 s
max. 32.00/Ñ ©©©©
3611 CHARACT.PH Back-up phase overcurrent characteristic
DEFINITE TIME [ ] Definite time
NORMAL INVERSE [ ] Normal inverse
VERY INVERSE [ ] Very inverse
EXTREMELY INVERS [ ] Extremely inverse
3612 I> Phase overcurrent threshold (DT) I>
min. 0.10 I/In
max. 4.00 I/In
max. 15.00 ©©©©
3613 T-I> Delay time for I> TI>
min. 0.00 s
max. 32.00/Ñ ©©©©
3614 Ip Phase o/c threshold (inverse time IDMT) Ip
min. 0.10 I/In
max. 4.00 ©©©©
3615 T-Ip Time multiplier for Ip (inverse time IDMT) Tp
min. 0.05 s
max. 32.00/Ñ ©©©©
©©©©©