7SG11 Argus 8 Description of Operation
The following event codes can be stored in the relay and will be time stamped to a resolution of 5ms. There can
be a maximum of 500 events stored in the event buffer as per the Argus range of relays. The Argus 8 events are
assigned to function code 167.
Event Description Frame
Type
Event Operation GI Code
Data Lost 1 RaisedOnly
0
Reset FCB 5 RaisedOnly
2
Reset CU 5 RaisedOnly
3
Start/Restart 5 RaisedOnly
4
Power On 5 RaisedOnly
5
External Trip 1 RaisedOnly
18
LED’s Reset 1 RaisedOnly
19
Trip Test 1 RaisedAndCleared
21
Settings Changed 1 RaisedAndCleared
22
Setting Group 1 Selected 1 RaisedAndCleared
23
Setting Group 2 Selected 1 RaisedAndCleared
24
Setting Group 3 Selected 1 RaisedAndCleared
25
Setting Group 4 Selected 1 RaisedAndCleared
26
Setting Group 5 Selected 1 RaisedAndCleared
35
Setting Group 6 Selected 1 RaisedAndCleared
36
Setting Group 7 Selected 1 RaisedAndCleared
37
Setting Group 8 Selected 1 RaisedAndCleared
38
Input 1 1 RaisedAndCleared
27
Input 2 1 RaisedAndCleared
28
Input 3 1 RaisedAndCleared
29
Input 4 1 RaisedAndCleared
30
Input 5 1 RaisedAndCleared
45
Input 6 1 RaisedAndCleared
46
Input 7 1 RaisedAndCleared
47
Input 8 1 RaisedAndCleared
48
Input 9 1 RaisedAndCleared
49
Output 1 1 RaisedAndCleared
51
Output 2 1 RaisedAndCleared
52
Output 3 1 RaisedAndCleared
53
Output 4 1 RaisedAndCleared
54
Output 5 1 RaisedAndCleared
55
Output 6 1 RaisedAndCleared
56
Output 7 1 RaisedAndCleared
57
Output 8 1 RaisedAndCleared
58
Output 9 1 RaisedAndCleared
59
Output 10 1 RaisedAndCleared
60
Output 11 1 RaisedAndCleared
61
Voltage Block 1 RaisedAndCleared
79
Waveform Stored 1 RaisedOnly
80
Remote CTRL Interrupted 1 RaisedOnly
81
Power On Counter Alarm 1 RaisedAndCleared
92
Trip Circuit Fail 1 RaisedAndCleared
20
Trip Count Alarm 1 RaisedAndCleared
33
General Alarm 1 1 RaisedAndCleared
121
General Alarm 2 1 RaisedAndCleared
122
General Alarm 3 1 RaisedAndCleared
123
©2011 Siemens Protection Devices Limited Chapter 1 Page 18 of 20