7SG11 Argus 8 Appendix
STATUS CONFIG MENU
SETTING RANGE SET VALUE
Settings Group Select S1..S9
(Note : special setting where each
status can be set from 1-8 to select
active group 1-8)
Inverted Inputs S1..S9
Gn VE1 Inhibit S1..S9
Gn VE2 Inhibit S1..S9
Gn VE3 Inhibit S1..S9
Gn VE4 Inhibit S1..S9
Gn 3VoE1 Inhibit S1..S9
Gn 3VoE2 Inhibit S1..S9
Gn V2E1 Inhibit S1..S9
Gn V2E2 Inhibit S1..S9
Gn FE1 Inhibit S1..S9
Gn FE2 Inhibit S1..S9
Gn FE3 Inhibit S1..S9
Gn FE4 Inhibit S1..S9
Gn Trip Circuit Fail S1..S9
Gn ALARM 1 S1..S9
Gn ALARM 2 S1..S9
Gn ALARM 3 S1..S9
Gn ALARM 4 S1..S9
Gn ALARM 5 S1..S9
Gn ALARM 6 S1..S9
Gn ALARM 7 S1..S9
Gn ALARM 8 S1..S9
Gn ALARM 9 S1..S9
Gn Waveform Trigger S1..S9
Gn Clock Sync. S1..S9
Gn Reset Outputs S1..S9
Gn Status 1 P/U Delay 0 – 2.00 sec step 10ms
2.10 – 20.00 sec step 100ms
21 – 300 sec step 1 sec
360 – 3600 sec step 60 sec
3900 – 14400 sec step 300 sec
Gn Status 1 D/O Delay As above
Gn Status 2 P/U Delay As above
Gn Status 2 D/O Delay As above
Gn Status 3 P/U Delay As above
Gn Status 3 D/O Delay As above
Gn Status 4 P/U Delay As above
Gn Status 4 D/O Delay As above
Gn Status 5 P/U Delay As above
Gn Status 5 D/O Delay As above
Gn Status 6 P/U Delay As above
Gn Status 6 D/O Delay As above
Gn Status 7 P/U Delay As above
Gn Status 7 D/O Delay As above
©2011 Siemens Protection Devices Limited Chapter 9 Page 7 of 13