7SG12 DAD N Relay Settings
©2010 Siemens Protection Devices Limited Chapter 3 Page 7 of 20
Description Range Default Setting
Aux I/P 17 Pickup Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 17 Dropoff Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 18 Pickup Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 18 Dropoff Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 19 Pickup Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 19 Dropoff Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 20 Pickup Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 20 Dropoff Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 21 Pickup Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 21 Dropoff Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 22 Pickup Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 22 Dropoff Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 23 Pickup Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 23 Dropoff Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 24 Pickup Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 24 Dropoff Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 25 Pickup Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 25 Dropoff Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 26 Pickup Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 26 Dropoff Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 27 Pickup Delay
1
0.000,0.005…864000 s 0 s
Aux I/P 27 Dropoff Delay
1
0.000,0.005…864000 s 0 s
1) Only when fitted.
1.8 Reylogic Element Menu
Description Range Default Setting
Max Data Rec Time
When a data record is triggered by a
fault condition the relay stops recording
information when either the triggering
condition is removed or this timer expires
whichever happens first.
0,1…60000 ms 2000 ms
1.9 Output Relay Menu
Description Range Default Setting
87/50-1 Phase A
Overall Differential INST/DTL Stage 1
Phase A element has operated
NONE, 1…29
1
NONE
87/50-1 Phase B NONE, 1…29
1
NONE
87/50-1 Phase C NONE, 1…29
1
NONE
87/50-2 Phase A
Overall Differential INST/DTL Stage 2
Phase A element has operated
NONE, 1…29
1
NONE
87/50-2 Phase B NONE, 1…29
1
NONE
87/50-2 Phase C NONE, 1…29
1
NONE
CT 50 Phase A
Overall Differential CT Supervision
INST/DTL Phase element has operated
NONE, 1…29
1
NONE
CT 50 Phase B NONE, 1…29
1
NONE
CT 50 Phase C NONE, 1…29
1
NONE
General Starter
A starter element is picked up. Useful
when testing individual functions!
NONE, 1…29
1
5
General Trip
An element has operated. Useful when
testing individual functions!
NONE, 1…29
1
4
Trip Cct Fail 1
Trip Circuit 1 has failed
NONE, 1…29
1
NONE
Trip Cct Fail 2
Trip Circuit 2 has failed
NONE, 1…29
1
NONE
Trip Circuit Fail
A trip circuit has failed.
NONE, 1…29
1
NONE