7SG12 DAD N Relay Settings
©2010 Siemens Protection Devices Limited Chapter 3 Page 17 of 20
Address Description
10128 CT Supervision Phase C
4.3 Registers
Address Description Format
30001 No. of Events In Store (See 434/TIR/15) 1 Register
30002 Latest Event Record (See 434/TIR/15) 8 Registers
Address Description Format
30010 Ia Primary FP_32BITS_3DP
1
30012 Ib Primary FP_32BITS_3DP
1
30014 Ic Primary FP_32BITS_3DP
1
30016 Ia Secondary FP_32BITS_3DP
1
30018 Ib Secondary FP_32BITS_3DP
1
30020 Ic Secondary FP_32BITS_3DP
1
30022 Ia Nominal FP_32BITS_3DP
1
30024 Ib Nominal FP_32BITS_3DP
1
30026 Ic Nominal FP_32BITS_3DP
1
30028 Fault Records UINT16
2
30029 Event Records UINT16
2
30030 Waveform Records UINT16
2
1) FP_32BITS_3DP: 2 registers - 32 bit fixed point, a 32 bit integer containing a value to 3 decimal places e.g. 50000 sent = 50.000
2) UINT16: 1 register - standard 16 bit unsigned integer
5 Reylogic Diagrams
General Trip
General_Trip
PhaseA_Trip
PhaseB_Trip
PhaseC_Trip
PhaseA_Starter
CT_50_Starter1
A87_50_1_Starter1
PhaseB_Starter
PhaseC_Starter
IEC Event Code 181-64
IEC Event Code 181-65
IEC Event Code 181-66
IEC Event Code 181-84
IEC Event Code 181-69
IEC Event Code 181-70
IEC Event Code 181-71
IEC Event Code 181-68
General Starter
General_Starter
STARTER LOGIC (Includes CT elements)
A87_50_1_Operated1
A87_50_1_Operated2
A87_50_1_Operated3
CT_50_Starter2
A87_50_1_Starter2
CT_50_Starter3
A87_50_1_Starter3
1
PhaseA_Starter
PhaseB_Starter
PhaseC_Starter
1
PhaseA_Trip
PhaseB_Trip
PhaseC_Trip
IntTriggerData
IntTriggerWavef orm
1A87_50_2_Starter1
1A87_50_2_Starter2
1A87_50_2_Starter3
1
A87_50_2_Operated1
A87_50_2_Operated2
1
1
A87_50_2_Operated3
GENERAL TRIP LOGIC