EasyManua.ls Logo

Siemens 7SR210

Siemens 7SR210
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
The copyright and other intellectual property rights in this document, and in any model or article produced from it
(and including any registered or unregistered design rights) are the property of Siemens Protection Devices
Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval
system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be
reproduced from this document unless Siemens Protection Devices Limited consent.
While the information and guidance given in this document is believed to be correct, no liability shall be accepted
for any loss or damage caused by any error or omission, whether such error or omission is the result of
negligence or any other cause. Any and all such liability is disclaimed.
©2011 Siemens Protection Devices Limited
7SR210 Non-Directional Relay
7SR220 Directional Relay
Applications Guide
(Software Version 2435H85008R7a-7a) (7SR210)
(Software Version 2435H85009R7a-7a) (7SR220)

Table of Contents

Other manuals for Siemens 7SR210

Question and Answer IconNeed help?

Do you have a question about the Siemens 7SR210 and is the answer not in the manual?

Siemens 7SR210 Specifications

General IconGeneral
BrandSiemens
Model7SR210
CategoryRelays
LanguageEnglish

Summary

Section 1: Common Functions

1.1 Multiple Settings Groups

Allows reconfiguring the relay for different system conditions like plant switching or load changes.

1.2 Binary Inputs

Input points programmable for relay functions, LEDs, or outputs, used for signals like inhibits, trip circuit status.

Effects of Capacitance Current on Binary Inputs

Discusses potential mal-operation of binary inputs due to capacitance current and methods for immunity.

AC Rejection for Binary Inputs

Default pick-up time delay of 20ms provides immunity to AC current induced from cross-site wiring.

1.3 Binary Outputs

Mapped to output functions via settings, used for trips, pick-up, plant control signals. All are trip rated.

1.4 LEDs

Output-function LEDs mapped to functions for status display (trips, pick-up). Can be self or hand reset.

Section 2: Protection Functions

2.1 Time Delayed Overcurrent (5151 G51 N)

Provides time/current operate characteristics, either IDMTL or DTL, for grading studies.

2.1.1 Selection of Overcurrent Characteristics

Explains using two independent characteristics for composite curves, two-stage tripping, or directionalization.

2.1.2 Reset Delay

Discusses reset delay for electromechanical relays and its importance for intermittent faults and auto-reclose schemes.

2.2 Voltage Dependent Overcurrent (51 V)

Reduced voltage indicates faults, used to make 51 elements more sensitive, applied to transformer incomers and long lines.

2.3 Cold Load Settings (51 c)

Uses alternative settings for cold load conditions after CB re-closure, typically higher than normal settings.

2.4 Instantaneous Overcurrent (5050 G50 N)

Independent setting for pick-up current and DTL for time grading and co-ordination.

2.4.1 Blocked Overcurrent Protection Schemes

Combines instantaneous and DTL elements for blocked schemes, improving fault clearance times over normally graded relays.

2.5 Sensitive Earth-Fault Protection (50 SEF)

Detects low-level earth faults, providing backup to main protection with a DTL characteristic.

2.6 Directional Protection (67)

Operates for faults in forward or reverse direction, defined by power flow relative to the busbar.

2 Out of 3 Logic

Used with directional overcurrent relays to prevent operation on single phase to earth faults when unbalanced voltage is present.

2.7 Directional Earth-Fault (5051 G, 5051 N, 5151 SEF)

Measures zero sequence current and compares it against zero phase sequence voltage for directional earth fault detection.

2.8 High Impedance Restricted Earth Fault Protection (64 H)

Detects low-level earth faults in transformer windings by monitoring unbalanced CT currents.

2.9 Negative Phase Sequence Overcurrent (46 NPS)

Detects unbalance in phase currents, indicating faults or unbalanced load, problematic for rotating plant.

2.10 Undercurrent (37)

Used in control logic for auto-changeover, auto-switching, and loss of load indication.

2.11 Thermal Overload (49)

Estimates real-time thermal state of cables/transformers based on past and present current levels.

2.12 UnderOver Voltage Protection (2759)

Detects abnormal undervoltage conditions due to overloads or system faults, and overvoltages that can damage insulation.

2.13 Neutral Overvoltage (59 N)

Detects earth faults where little or no earth current flows, often due to HV feeder trip at HV side.

2.13.1 Application with Capacitor Cone Units

Cost-effective method for deriving residual voltage using capacitor cones and external adaptor units.

2.13.2 Derived NVD Voltage

NVD voltage derived from three phase to neutral voltages; may mal-operate during VT Fail condition.

2.14 Negative Phase Sequence Overvoltage (47)

Detects phase unbalances, used for monitoring busbar supply quality rather than detecting system faults.

2.15 UnderOver Frequency (81)

Implemented for load shedding based on frequency deviations, typically for generator-load balance.

Section 3: CT Requirements

3.1 CT Requirements for Overcurrent and Earth Fault Protection

Specifies CT classes (10P10, 5P20) and VA ratings for industrial and utility systems.

3.1.1 Overcurrent Protection CTs

Details CT classes (10P10, 5P20) and VA ratings for industrial and utility distribution networks.

3.1.2 Earth Fault Protection CTs

Earth fault protection uses same CTs as phase fault; requirements are less onerous than for overcurrent.

3.2 CT Requirements for High Impedance Restricted Earth Fault Protection

Recommends low reactance CTs (IEC 60044 Class PX) for high impedance REF, with identical turns ratios and knee point voltage.

Section 4: Control Functions

4.1 Auto-reclose Applications

Automatic reclosing for transient faults on overhead lines to minimize supply loss and manual intervention.

4.1.1 Auto-Reclose Example 1

Provides 4 phase fault recloses (2 instantaneous, 2 delayed) and 2 SEF recloses.

4.1.2 Auto-Reclose Example 2 (Use of Quicklogic with AR)

Demonstrates auto-reclose sequence with 2 instantaneous and 2 delayed recloses using Quicklogic.

4.2 Quick Logic Applications

Applications of quick logic for control functions, enabling flexible scheme configuration.

4.2.1 Auto-Changeover Scheme Example

Illustrates an auto-changeover scheme where CB3 closes to re-supply loads after an incomer fault is isolated.

Section 5: Supervision Functions

5.1 Circuit-Breaker Fail (50 BF)

Detects circuit breaker failure to operate, initiating re-trip or back-trip actions to clear faults.

5.2 Current Transformer Supervision (60 CTS)

Detects CT failures by monitoring unbalanced currents and NPS voltage to differentiate from system faults.

5.3 Voltage Transformer Supervision (60 VTS)

Supervises VT integrity, detecting failures via unbalanced voltages and NPS current to avoid misoperation.

5.4 Trip-Circuit Supervision (74 TCS)

Monitors integrity of the CB trip circuit wiring, providing alarms for failures.

5.4.1 Trip Circuit Supervision Connections

Details connections for trip circuit supervision (schemes H5, H6, H7) to monitor wiring integrity.

5.5 Inrush Detector (81 HBL2)

Detects high levels of 2nd Harmonic current indicating transformer inrush, preventing incorrect trip commands.

5.6 Broken Conductor Load Imbalance (46 BC)

Detects open circuit or load imbalance using NPS current, indicating a broken conductor condition.

5.7 Circuit-Breaker Maintenance

Provides counters for CB trip, wear, and frequent operation to estimate maintenance needs.

Related product manuals