EasyManuals Logo

Siemens 7SR210 User Manual

Siemens 7SR210
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
7SR210 & 7SR220 Applications Guide
The Effects of Capacitance Current
The binary inputs have a low minimum operate current and may be set for instantaneous operation. Consideration
should be given to the likelihood of mal-operation due to capacitance current. Capacitance current can flow
through the BI for example if an earth fault occurs on the dc circuits associated with the relay. The binary inputs
will be less likely to mal-operate if they:
1 Have both the positive and negative switched (double-pole switched).
2 Do not have extensive external wiring associated with them e.g. if the wiring is confined to the
relay room.
Where a binary input is both used to influence a control function (e.g. provide a tripping function) and it is
considered to be susceptible to mal-operation the external circuitry can be modified to provide immunity to such
disturbances, see fig 1.2-2.
AC Rejection
The default pick-up time delay of 20ms provides immunity to ac current e.g. induced from cross site wiring.
©2011 Siemens Protection Devices Limited Page 7 of 40

Table of Contents

Other manuals for Siemens 7SR210

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 7SR210 and is the answer not in the manual?

Siemens 7SR210 Specifications

General IconGeneral
BrandSiemens
Model7SR210
CategoryRelays
LanguageEnglish

Related product manuals