EasyManua.ls Logo

Siemens 7SR210 - Typical Connection: 7 SR22 Directional OC and EF; Figure 7.5-1 7 SR22 Applied to Feeder - no Zero Sequence Voltage Source

Siemens 7SR210
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR210 & 7SR220 Installation Guide
7.5 Typical Connection: 7SR22 Directional OC and EF
L1 L2 L3
A
C
B
S1
S2
P1
P2
I
L1
(I
A
)
1
2
5
6
9
10
13
14
A
17
18
19
20
21
22
23
24
25
26
27
28
1A
5A
1A
5A
1A
5A
1A
5A
15
16
11
12
1A
5A
3
4
7
8
B
C
V
4
(V
X
)
V
L3
(V
C
)
V
L2
(V
B
)
V
L1
(V
A
)
I
L2
(I
B
)
I
L3
(I
C
)
I
4
(I
G
)
I
5
(I
SEF
)
NOTES
1) CT circuits are shown connected to 1A tap – use alternative tap for 5A rated CTs.
2) CT and Earth connections are typical only.
3) Vee Connected VT: Phase Voltage Config:-VA,VB,VC
4) DEF elements must be NPS polarised (Vo polarising not applicable)
Figure 7.5-1 7SR22 Applied to Feeder - No Zero Sequence Voltage Source
©2011 Siemens Protection Devices Limited Page 23 of 24

Table of Contents

Other manuals for Siemens 7SR210

Related product manuals