English 7XR6004
6 C53000-B119U-C137-1
Unpacking and Re-packing
When dispatched from the factory, the equipment is packed in accordance with the guide-
lines laid down in IEC 60 255–21 which specify the impact resistance of packaging.
This packing shall be removed with care, without force and without the use of inappropriate
tools. The equipment should be visually checked to ensure that there are no external traces
of damage.
Please observe absolutely all notes and hints which may be enclosed in the packaging.
Before initial energization with supply voltage, or after storage, the relay shall be situated in
the operating area for at least two hours in order to ensure temperature equalization and to
avoid humidity influences and condensation.
For further transport, the transport packing can be re-used when applied in the same way.
The storage packing of the individual relays is not suited for transport. If alternative packing
is used, this must also provide the same degree of protection against mechanical shock and
vibration as laid down in IEC 60255-21-1 class 2 and IEC 60255-21-2 class 1.
Storage
The device should be stored in dry and clean rooms. The limit temperature range for storage
of the relays or associated spare parts is -25 °C to +55 °C, corresponding to -13 °F to 131 °F.
The relative humidity must be within limits such that neither condensation nor ice forms.