English 7XT3300-0*A00/DD
22 C53000-B119U-C129-1
Climatic Stress Tests
Temperatures
Perm
Humidity
All devices shall be installed such that they are not exposed to direct sunlight, nor subject to large fluctiations in temperature that may cause
Housing
Standards IEC 60255-6
Permissible temporary operating tempera-
ture (tested for 96 h)
–25 °C to +70 °C
Recommended for continuous operation
(acc. to IEC 60255-6)
–5 °C to +55 °C
Limit temperatures for storage –25 °C to +55 °C
Limit temperatures during transport –25 °C to +70 °C
Storage and transport of the device with factory packaging!
Admissible humidity Annual average 75 % relative humidity;
on 56 days of the year up to 93 % relative
humidity. Condensation must be avoided in
operation!
All devices shall be installed such that they are not exposed to direct sunlight, nor subject
to large fluctuations in temperature that may cause condensation.
Dimensions See figures 5 and 6
Mass
Approx. 6.1 kg
Degree of protection according to EN 60529
IP20
Note
With maximum power output, the device has a power loss of approx.
24 W. To ensure unhindered heat dissipation through the vent holes,
the distance to other devices located at the top and bottom must be at
least 100 mm. This device must therefore always be mounted in the
bottom part of the cabinet.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 7XT3300-0 A00/DD Series and is the answer not in the manual?

Siemens 7XT3300-0 A00/DD Series Specifications

General IconGeneral
BrandSiemens
Model7XT3300-0 A00/DD Series
CategoryPortable Generator
LanguageEnglish

Related product manuals