17/30
Smart Infrastructure CC1N7544en
21.05.2021
Technical Data
Safety class I with parts according to II and III to
Degree of protection IP00 to EN 60529:1991 + A1:2000 +
A2:2013
Note
The burner or boiler manufacturer must
ensure degree of protection IP40 for
LMV36 as per EN 60529:1991 + A1:2000
through adequate installation.
Mode of operation Type 2B in accordance with
Rated surge voltage In accordance with EN 60730-1:2016,
Voltage and current for the purposes of
the EMC emitted interference tests
The emitted interference measurement
test takes place with mains voltage and
maximum power consumption
Permissible primary fuse (Si) (external)
Caution!
Risk of damage to the switching contacts!
If the external primary fuse (Si) is blown due to overload or short-circuit at the
current depending on the operating state of the unit
Safety shutdown from operating
Approx. AC 93 V
Restart on rise in mains voltage
Status inputs: Status inputs (with the exception of the safety loop) of the contact
feedback network (KRN) are used for system supervision and require mains-related
Input currents and input voltages
- UeMax
- UeMin
- IeMax
UN +10%
UN -15%
1,5 mA peak
Contact material recommendation for
external signal sources (air pressure
switch, pressure switch-min, pressure
Gold-plated silver contacts
Transition / settling behavior / bounce
- Perm. bounce time of contacts
Max. 50 ms (after the bounce time,
contact must stay closed or open)
Voltage detection
- On
AC 90…132 V
Terminal loading