Technical Data
Mains voltage
AC 120 V
-
15%
/ +10%
Mains freque
ncy
50 / 60 Hz
±
6%
Power consumption
<30 W (typically)
Safety class I with parts according to II and III to
EN 60730
-
1
:
2
0
1
6
Degree of protection IP00 to EN 60529:1991 + A1:2000 +
A2:2013
Note
The burner or boiler manufacturer must
ensure degree of protection IP40 for
LMV36 as per EN 60529:1991 + A1:2000
+ A2:2013
through adequate installation.
Mode of operation Type 2B in accordance with
EN 60730
-
1
:
2
0
1
6
Rated surge voltage In accordance with EN 60730-1:2016,
section 20 (OC III
)
Voltage and current for the purposes of
the EMC emitted interference tests
The emitted interference measurement
test takes place with mains voltage and
maximum power consumption
Permissible primary fuse (Si) (external)
Max.
16
AT
Caution!
Risk of damage to the switching contacts!
If the external primary fuse (Si) is blown due to overload or short-circuit at the
terminals, the
LMV
36
must be replaced.
Unit fuse F1 (i
n
ternal)
6
.
3 AT (
IEC
60127
-
2
:2014
)
Mains sup
pl
y: Input
current depending on the operating state of the unit
Undervoltage
Safety shutdown from operating
p
o
sition at mains voltage
Approx. AC 93 V
Restart on rise in mains voltage
Approx. AC 96 V
Status inputs: Status inputs (with the exception of the safety loop) of the contact
feedback network (KRN) are used for system supervision and require mains-related
input voltage
Input safety loop
Refer to
Terminal loading outputs
Input currents and input voltages
- UeMax
- UeMin
- IeMax
-
IeMin
UN +10%
UN -15%
1,5 mA peak
0,7 mA peak
Contact material recommendation for
external signal sources (air pressure
switch, pressure switch-min, pressure
switch
-
max, etc.)
Gold-plated silver contacts
Transition / settling behavior / bounce
- Perm. bounce time of contacts
when s
witching on / off
Max. 50 ms (after the bounce time,
contact must stay closed or open)
UN
AC 120 V
Voltage detection
- On
-
Off
AC 90…132 V
<AC 40 V
Basic unit LMV36
General
Terminal loading
«I
n
puts»