CM 1542-1
Operating Instructions, 07/2019, C79000-G8976-C355-04
11
Properties and functions
1
1.1 Communication services
The CM supports the following communications services:
PROFINET IO
PROFINET IO allows direct access to IO devices over Industrial Ethernet.
Real-Time communication (RT)
Isochronous Real-Time communication (IRT)
Media redundancy MRP
Device replacement without exchangeable storage medium
IO controller
IO device (iDevice, Shared Device, Prioritized startup)
Isochronous real time
Open User Communication
Open User Communication supports the following communications services via the CM
using programmed or configured communications connections:
TCP (complying with RFC 793), ISO-on-TCP (complying with RFC 1006) and UDP
(complying with RFC 768)
With the interface via TCP connections, the CM supports the socket interface to
TCP/IP available on practically every end system.
Multicast with UDP
The multicast mode is made possible by selecting a suitable IP address when
configuring connections. A maximum of six multicast groups are supported via UDP.
S7 communication
PG communication
Operator control and monitoring functions (HMI communication)
Data exchange over S7 connections