&RQILJXULQJ
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
5-42 A5E00105492-03
/RQJHUFDEOHOHQJWKV
If you want to implement cable lengths above those permitted in a segment, you
must use RS485 repeaters. Information on this topic can be found in the
RS485 repeater product information.
/HQJWKRIWKHVWXEFDEOHV
If bus nodes are connected to a bus segment via stub cables (e.g. PG via a normal
PG cable), then you must consider the maximum possible length of the stub cable.
The following table lists the maximum permitted lengths of stub cables per
segment:
Table 5-26 Stub cable lengths per segment
1XPEHURIQRGHVZLWKVWXEFDEOHOHQJWK
RI
7UDQVPLVVLRQUDWH 0D[OHQJWKRIVWXE
FDEOHVSHUVHJPHQW
PRUP 0
9.6 kbps to 93.75
kbps
M 96 32 32
187.5 kbps M 75 32 25
500 kbps M 30 20 10
1.5 Mbps M 10 6 3
3 Mbps to 12 Mbps
1) 1) 1)
1)
At 3 Mbps and higher, use the PG patch cord (Order No. 6ES7 901-4BD00-0XA0) to
connect the PG or PC. You can use multiple PG patch cords of this number in an
installation. Do not use any other type of stub cable.

Table of Contents

Other manuals for Siemens CPU 313C-2 DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 313C-2 DP and is the answer not in the manual?

Siemens CPU 313C-2 DP Specifications

General IconGeneral
BrandSiemens
ModelCPU 313C-2 DP
CategoryProcessor
LanguageEnglish

Related product manuals