Cycle and reaction times
5.2 Cycle time
CPU 31xC and CPU 31x, Technical Data
5-6 Manual, 01/2006 Edition, A5E00105475-06
Operating system processing time at the scan cycle check point
The table below shows the operating system processing time at the scan cycle checkpoint of
the CPUs. These times are calculated without taking into consideration times for:
Testing and commissioning routines, e.g. status/controlling of variables or block status
functions
Transfer and deletion of blocks, compressing user program memory
Communication
Writing, reading of the SIMATIC Micro Memory Card with SFC 82 to 84
Table 5-6 Operating system processing time at the scan cycle check point
CPU Cycle control at the scan cycle check point (CCP)
312C 500 μs
313C 500 μs
313C-2 500 μs
314C-2 500 μs
312 500 μs
314 500 μs
315 500 μs
317 150 μs
319 77 μs
Extension of the cycle time as a result of nested interrupts
Enabled interrupts also extend cycle time. Details are found in the table below.
Table 5-7 Extended cycle time due to nested interrupts
Interrupt type Process
interrupt
Diagnostic
Interrupt
Time-of-day
interrupt
Delay interrupt Watchdog
interrupt
312C 700 μs 700 μs 600 μs 400 μs 250 μs
313C 500 μs 600 μs 400 μs 300 μs 150 μs
313C-2 500 μs 600 μs 400 μs 300 μs 150 μs
314C-2 500 μs 600 μs 400 μs 300 μs 150 μs
312 700 μs 700 μs 600 μs 400 μs 250 μs
314 500 μs 600 μs 400 μs 300 μs 150 μs
315 500 μs 600 μs 400 μs 300 μs 150 μs
317 190 μs 240 μs 200 μs 150 μs 90 μs
319 72 μs 87 μs 39 μs 26 μs 10 μs
The program runtime at interrupt level must be added to this time extension.

Table of Contents

Other manuals for Siemens CPU 315-2 DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 315-2 DP and is the answer not in the manual?

Siemens CPU 315-2 DP Specifications

General IconGeneral
Memory64 KB
Power Supply24 V DC
Order Number6ES7 315-2AG10-0AB0
Number of DP Masters1
Number of DP Slaves124
Load Memory64 KB
Number of Timers256
Number of Counters256
Data Memory64 KB
Operating Temperature0 to 60 °C
Integrated InterfacesMPI, DP
Digital OutputsNot integrated
Analog InputsNot integrated
Analog OutputsNot integrated
Programming LanguagesLAD, FBD, STL
Digital InputsNot integrated
Weight660 g