Cycle and reaction times
5.2 Cycle time
CPU 31xC and CPU 31x, Technical Data
5-8 Manual, 01/2006 Edition, A5E00105475-06
Block processing times may fluctuate
Fluctuation of the block processing time (e.g. OB 1) may also be a factor causing cycle time
fluctuation, due to:
conditional instructions,
conditional block calls,
different program paths,
loops etc.
Maximum cycle time
In
STEP 7
you can modify the default maximum cycle time. OB80 is called on when this time
expires. In this block you can specify the CPUs response to this timeout error. The CPU
switches to STOP mode if OB80 does not exist in its memory.
5.2.4 Communication load
Configured communication load for PG/OP communication, S7 communication and PROFINET CBA
The CPU operating system continuously provides a specified percentage of total CPU
processing performance (time-sharing technology) for communication tasks. Processing
performance not required for communication is made available to other processes. In HW
Config, you can specify a communication load value between 5% and 50%. Default value is
20%.
You can use the following formula for calculating the cycle time extension factor:
100 / (100 – configured communication load in %)
7LPHVOLFHPV
2SHUDWLQJV\VWHP
8VHUSURJUDP
&RPPXQLFDWLRQV
6KDUHFDQEHFRQILJXUHG
EHWZHHQDQG
,QWHUUXSWLRQ
RIXVHUSURJUDP
Example: 20 % communication load
In your hardware configuration, you have specified a communication load of 20 %. The
calculated cycle time is 10 ms. Using the above formula, the cycle time is extended by the
factor 1.25.

Table of Contents

Other manuals for Siemens CPU 315-2 DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 315-2 DP and is the answer not in the manual?

Siemens CPU 315-2 DP Specifications

General IconGeneral
Memory64 KB
Power Supply24 V DC
Order Number6ES7 315-2AG10-0AB0
Number of DP Masters1
Number of DP Slaves124
Load Memory64 KB
Number of Timers256
Number of Counters256
Data Memory64 KB
Operating Temperature0 to 60 °C
Integrated InterfacesMPI, DP
Digital OutputsNot integrated
Analog InputsNot integrated
Analog OutputsNot integrated
Programming LanguagesLAD, FBD, STL
Digital InputsNot integrated
Weight660 g

Related product manuals