Cycle and reaction times
5.3 Response time
CPU 31xC and CPU 31x, Technical Data
Manual, 01/2006 Edition, A5E00105475-06
5-13
Tips and notes
The upper graphic already includes the use of uniform values for the transfer frequency of all
interconnections to a partner.
The performance can drop by up to 50 % if the values are distributed to different
frequency levels.
The use of data structures and arrays in an interconnection instead of many single
interconnections with simple data structures increases the performance.
5.3 5.3 Response time
5.3.1 Overview
Definition of response time
The response time is the time between the detection of an input signal and the change of a
linked output signal.
Fluctuation width
The physical response time lies between the shortest and the longest response time. You
must always reckon with the longest response time when configuring your system.
The shortest and longest response times are shown below, to give you an idea of the
fluctuation width of the response time.
Factors
The response time depends on the cycle time and following factors:
Delay of the inputs and outputs of signal modules or integrated I/O.
Additional update times for PROFINET IO
additional DP cycle times on PROFIBUS DP
Execution in the user program
Reference
The delay times are located in the specifications of the signal modules (
Module data
Reference Manual).
Update times for PROFINET IO
If you configured your PROFINET IO system in STEP 7, STEP 7 calculates the update time
for PROFINET IO. You can then view the PROFINET IO update times on your PG.

Table of Contents

Other manuals for Siemens CPU 315-2 DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 315-2 DP and is the answer not in the manual?

Siemens CPU 315-2 DP Specifications

General IconGeneral
Memory64 KB
Power Supply24 V DC
Order Number6ES7 315-2AG10-0AB0
Number of DP Masters1
Number of DP Slaves124
Load Memory64 KB
Number of Timers256
Number of Counters256
Data Memory64 KB
Operating Temperature0 to 60 °C
Integrated InterfacesMPI, DP
Digital OutputsNot integrated
Analog InputsNot integrated
Analog OutputsNot integrated
Programming LanguagesLAD, FBD, STL
Digital InputsNot integrated
Weight660 g