53WL Circuit Breaker Selection and Application Guide
WL Power Circuit Breaker Cradles
UL 1066 Listed Cradle Catalog Number 
  Type of secondary terminal connection 
1
 
  For Breakers:   
     Screw clamp terminals                         P  
     Spring clamp terminals                         T  
     Ring terminals                          R  
     Screw clamp terminals (low profile, non-partable design)                 K 
  For Switch (Non-automatic):
     Screw clamp terminals                         D
     Spring clamp terminals                         E  
     Ring terminals                          F  
     Screw clamp terminals, non-partable design)                  M
  Truck Operated Contacts (TOC)                        
  Breaker position switches in the following configurations:       
 None                      X  
  (1) Connected, (1) Test, (1) Disconnected - all Form C                  1  
  (3) Connected, (2) Test, (1) Disconnected - all Form C                  3  
  (6) Connected - all Form C                          6
  Cradle mounted key locks 
2
 
 None                       X  
  Lock breaker in OPEN position (Kirk key)                        A  
  Lock breaker in OPEN position (Superior key)                      B  
  Double lock breaker in OPEN position (Kirk key)                      C  
  Double lock breaker in OPEN position (Superior key)                    D  
  Provision only - Lock breaker in OPEN position                      E  
  Provision only - Double lock breaker in OPEN position                    F
 
Primary conductor isolation shutter
  None                                  X  
 Isolation Shutters                    F
 
 
 
                   Cradle catalog number
                 
G   2   3   4   5   6   7   8   9   10 11 12 13  14  15  
  Class   Interrupt rating (kA)  Frame  Frame size   
   240VAC       Max ampere         
     480VAC   600VAC  rating  (A)  2  3 
  N    50    50    800  X     N   2   3  0  8  
  N    50    50   1600  X     N    2   3  1   6  
  S    65    65    800  X     S   2   3  0  8  
  S    65    65   1600  X     S   2   3  1   6  
  S    65    65  2000   X     S   2   3  2  0  
  S    65    65  3200   X     S   2   3  3  2  
  H    85    65    800  X     H   2   3  0  8  
  H    85    65  1600   X     H   2   3  1  6  
  H    85    65   2000  X     H   2   3  2  0  
  H    85    65   3200  X     H   2   3  3  2  
  H    85    85  4000     X   H   3   3  4  0  
  H    85    85   5000    X   H   3   3  5  0  
  L   100    85    800  X     L   2   3  0  8  
  L   100    85   1600  X     L   2   3  1  6  
  L   100    85   2000  X     L   2   3  2  0  
  L   100    85   3200  X     L   2   3  3  2  
  L   100    85   4000    X   L   3   3  4  0  
  L   100    85   5000    X   L   3   3  5  0  
  M  150    85  3200     X   M   3   3  3  2  
  M  150    85  4000     X   M   3   3  4  0  
  M   150    85  5000     X   M   3   3  5  0  
  F  200   200    800  X     F   2   3  0  8  
  F  200   200   1600  X     F   2   3  1  6  
  F  200   200   2000  X     F   2   3  2  0  
  F  200   200   3200    X   F   2   3  3  2 
  F  200   200   4000    X   F   3   3  4  0  
  F  200   200   5000    X   F   3   3  5   0
Interrupting rating, frame size and frame rating
 
1 
Terminal blocks (X5, X6, X8, X9) are installed as standard.
 
2
 Fused Frame Size 3 circuit breakers include a two cylinder provision as standard, with the second position pre-populated with a key-interlock to prevent racking  
  (in or out) of the separately-mounted fuse carriage while the associated fused circuit breaker is closed.
Courtesy of NationalSwitchgear.com