Building Technologies
CPS Fire Safety
Technical data
FC121-ZA FC122-ZA FC123-ZA FC124-ZA
Mains voltage AC 196…253 V AC 97…127 V
AC 196…253 V
Power consumption 25 W 70 W
Operating voltage DC 21…28.6 V
Max. nominal output current without battery
charging (I max b)
Max. 0.9 A Max. 2.5 A
Battery capacity 2x 12 V, up to 7 Ah 2x 12 V, up to 17 Ah
Battery monitoring Yes Yes
Mains monitoring Yes Yes
Connectable detector series 110-series / DS11 / SynoLINE300/600
Number of lines 2 4 8 12
Number of detectors per line Max. 32
Integrated inputs/outputs
Monitored outputs
RT Alarm
Horn
Dry contact
RT fault
Free programmable inputs/outputs
1x 24 V / 0.5 A
1x 24 V / 0.5 A
30 V / 1 A
2
1x 24 V / 1 A
1x 24 V / 1 A
30 V / 1 A
3
Slots for relay cards 1 2 3
Emergency current Up to 72 Ah
Operating temperature -5…+40 °C
Storage temperature -20…+60 °C
Humidity (no condensation permitted) 95 % rel.
Dimensions (W x H x D) 360 x 310 x 85 mm 430 x 399 x 124 mm
Color
Housing and Cover Grey, ~RAL 000 50 00
Protection category (IEC 60529) IP30 IP30
Approvals
LPCB 531q/01 531q/02

Other manuals for Siemens FC123-ZA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FC123-ZA and is the answer not in the manual?

Siemens FC123-ZA Specifications

General IconGeneral
BrandSiemens
ModelFC123-ZA
CategoryControl Panel
LanguageEnglish

Related product manuals