8 A6V11274135_en--_b
Technical data
Environmental
Operating temperature -32-120°F (0-49°C)
Relative humidity - Up to 93% @ 90°F (32°C)
To be installed in an indoor dry protected environment
only
Primary Power Supply (FP2011-U1)
Input: 120 VAC, 60 Hz or 240 VAC, 50 Hz
@ 2.0 A max.
Supervised
Output: 26 VDC @ 6.5 A max.
Max current: 6.5 A (2 hours max.)
Filtered and Regulated
Secondary Power Supply
24 V lead-acid battery set
Max. charged voltage: 27.8 VDC
Automatic low battery disconnect voltage: 19.2±0.1 VDC
Max. charge current: 0.45 A
Battery capacity:12 AH internally to 18 AH with separate
enclosure FH2072-UA
Supervised
Auxiliary Power Outputs
Non-resettable power output Resettable power output
Power limited Power limited
Current: 0.75 A Current: 0.75 A
Voltage: 19 to 28 VDC Voltage: 19 to 28 VDC
Ripple: 0.1 VAC Ripple: 0.1 VAC
Special Application Special Application
Status Relays
Non-power limited
One programmable relay
Three non-programmable relays: Trouble, Supervisory,
Alarm
Contact rating: 2 A, 30 VDC maximum
Form C contact
Notification Appliance Circuits
Power limitedSupervised
Current Draw Maximum Line Resistance
2.5 A 3.2 Ω
2.0 A 4.0 Ω
1.5 A 5.3 Ω
1.0 A 8.0 Ω
0.5 A 16.0 Ω
Alarm voltage: 16 to 32 VDC
Maximum ripple: 0.1 VAC
Used for special application only
Two Class B or one Class A
Total Max. Current: 2.5 A
Serial Interface Circuit (UFP)
Power limited
Supervised
Maximum wire loop resistance: 50 Ω total
Physical layer: RS485
SLC Addressable Device Circuits
Max. 32 VDC
Power limited
Supervised
Max. current: 0.07 A (RMS)
Maximum wire loop resistance: 50 Ω
Two Class B or one Class A circuit
Max. 50 addressable devices
City Tie Circuits
Supply Input:
Voltage: 26 VDC / 18 – 28 VDC for battery
Current: Max. 0.4 A
Supervised
Output:
City Tie-Output 1
Normal output voltage: 19-28 VDC (open circuit condition)
Supervisory current: 1 mA
Maximum trip current: 400 mA
Maximum coil plus wire resistance: 22.5
Leased line-Output 1
Normal output voltage: 19-28 VDC (open circuit condition)
Trouble output voltage: 0 V
Alarm output voltage: -(19-28) VDC (open circuit condition)
Maximum wire resistance: 2-5 K
Maximum short circuit current: 25 mA
Leased line-Output 2
Normal output voltage: 19-28 VDC (open circuit condition)
Supervisory output voltage: -(19-28) VDC (open circuit
condition)
Maximum wire resistance: 2-5 K
Maximum short circuit current: 25 mA
DACT Circuits
Power limited
Supervised for short or open circuit conditions
Compliance to FCC part 68
Support RJ31X connection
Compatible Digital Alarm Communication Receiver
(DACR) list,
Device Module
MX8000 Honeywell
CAUTION:
· To reduce the risk of fire, use only No. 26 AWG
or larger telecommunication line cord.
· Only to a loop start telephone circuit and not to a
ground start telephone circuit.
· To verify the integrity of the call forwarding
feature every 24 hours.
firealarmresources.com