8 A6V11274135_en--_b
Technical data
Environmental
Operating temperature -32-120°F (0-49°C)
Relative humidity - Up to 93% @ 90°F (32°C)
To be installed in an indoor dry protected environment
only
Primary Power Supply (FP2011-U1)
Input: 120 VAC, 60 Hz or 240 VAC, 50 Hz
@ 2.0 A max.
Supervised
Output: 26 VDC @ 6.5 A max.
Max current: 6.5 A (2 hours max.)
Filtered and Regulated
Secondary Power Supply
24 V lead-acid battery set
Max. charged voltage: 27.8 VDC
Automatic low battery disconnect voltage: 19.2±0.1 VDC
Max. charge current: 0.45 A
Battery capacity:12 AH internally to 18 AH with separate
enclosure FH2072-UA
Supervised
Auxiliary Power Outputs
Non-resettable power output Resettable power output
Power limited Power limited
Current: 0.75 A Current: 0.75 A
Voltage: 19 to 28 VDC Voltage: 19 to 28 VDC
Ripple: 0.1 VAC Ripple: 0.1 VAC
Special Application Special Application
Status Relays
Non-power limited
One programmable relay
Three non-programmable relays: Trouble, Supervisory,
Alarm
Contact rating: 2 A, 30 VDC maximum
Form C contact
Notification Appliance Circuits
Power limitedSupervised
Current Draw Maximum Line Resistance
2.5 A 3.2 Ω
2.0 A 4.0 Ω
1.5 A 5.3 Ω
1.0 A 8.0 Ω
0.5 A 16.0 Ω
Alarm voltage: 16 to 32 VDC
Maximum ripple: 0.1 VAC
Used for special application only
Two Class B or one Class A
Total Max. Current: 2.5 A
Serial Interface Circuit (UFP)
Power limited
Supervised
Maximum wire loop resistance: 50 Ω total
Physical layer: RS485
SLC Addressable Device Circuits
Max. 32 VDC
Power limited
Supervised
Max. current: 0.07 A (RMS)
Maximum wire loop resistance: 50 Ω
Two Class B or one Class A circuit
Max. 50 addressable devices
City Tie Circuits
Supply Input:
Voltage: 26 VDC / 18 – 28 VDC for battery
Current: Max. 0.4 A
Supervised
Output:
City Tie-Output 1
Normal output voltage: 19-28 VDC (open circuit condition)
Supervisory current: 1 mA
Maximum trip current: 400 mA
Maximum coil plus wire resistance: 22.5 Ω
Leased line-Output 1
Normal output voltage: 19-28 VDC (open circuit condition)
Trouble output voltage: 0 V
Alarm output voltage: -(19-28) VDC (open circuit condition)
Maximum wire resistance: 2-5 KΩ
Maximum short circuit current: 25 mA
Leased line-Output 2
Normal output voltage: 19-28 VDC (open circuit condition)
Supervisory output voltage: -(19-28) VDC (open circuit
condition)
Maximum wire resistance: 2-5 KΩ
Maximum short circuit current: 25 mA
DACT Circuits
Power limited
Supervised for short or open circuit conditions
Compliance to FCC part 68
Support RJ31X connection
Compatible Digital Alarm Communication Receiver
(DACR) list,
MX8000 Honeywell
CAUTION:
· To reduce the risk of fire, use only No. 26 AWG
or larger telecommunication line cord.
· Only to a loop start telephone circuit and not to a
ground start telephone circuit.
· To verify the integrity of the call forwarding
feature every 24 hours.