CAN Circuits – connection of the Voice panels to remote or local CAN modules (VTO2001-U2, VTO2004-U2, VCI2001-
U1). This can be configured as Class B. Refer to the FS20 Mounting, Installation and Product Data manual, Document ID
A6V10315015, for proper wiring connection.
Ethernet Connections – This is the internal connection of the Card cage (4 amplifiers) (VCA2002-A1) to the Op. unit
bracket UL (option) (FCM2025/2050-A1) and VCNET connection of the FV2025/2050 Control Panel. For inter-connection
between FC2025/FC2050 and FV2025/FV2050, the Ethernet switch (modular) (FN2012-A1, S54400-B152-A1) must be
used. The Ethernet connections can be configured as Class B or Class X and is supervised. For proper wiring connection,
refer to the FN2012-A1 Installation Instructions, Document ID A6V10407862.
Audio Input/Output – This is the internal and external connection of audio inputs from microphones and connected audio
systems. All audio inputs and outputs are Class B and are supervised. Refer to the FS20 Mounting, Installation and
Product Data manual, Document ID A6V10315015, for proper wiring connection.
Speaker Circuits – This is the external connection of amplified audio to the speaker lines. These can be configured as
Class A, Class B or Dual-interleaved Class B and are supervised. Refer tothe VCI2001-U1 Voice amplifiercard (25V)
Installation Instructions, Document ID A6V10370410, for proper wiring connection. Up to 24 HCP intelligent control points
can be used in speaker zones and can be configured as Class A or Class B. Refer to the HCP installation instructions,
P/N 315-034860, for more information.
Compatible Solenoids – Refer to the Solenoid Compatibility List, Document ID A6V11620059.
Note: The Manual Discharge function always overrides the Abort switch function.
Leased Line / City Tie Circuit – This is the connection of FACP to the Leased Line or City Tie through optional LLCT
Module (FCI2020-U1). This is configured as Class B only and is supervised only when configured as City Tie. Refer to the
FS20 Mounting, Installation and Product Data manual, Document ID A6V10315015, Section 23, for proper wiring
connection.
Central/Remote Station – The FACP uses the Dialer module (DACT) (FCA2015-U1) connected to the PSTN to connect to
the central or remote station in the event of life safety situation. Connections to phone lines are supervised. Refer to the
FS20 Mounting, Installation and Product Data manual, Document ID A6V10315015, for proper wiring connection.
For Canadian Installations the following applies:
- Both the Dialer module (DACT) (FCA2015-U1) and the 3rd party communicator must be configured and
connected to the same Central Station.
- One of the User-Defined buttons on the Operating Unit must be programmed as
Manual Alarm Signal
(evacuation) Control
which is able to initiate alarm signal and resound audible devices after they have been
silenced. The button chosen must be clearly marked on the Inscription Strip.
- The Battery disconnect module (FCA2032-U1) is required to disconnect the battery when voltage drops below 19
VDC while system is on battery power.
- If using a Remote display or Remote Terminal (FT2014-U2 or FT2015-U2) the Inner Door RDT (FHD2012-U1) is
required to meet ULC audible indicator sound output requirements.