Appendix G: Default settings for panel/devices
21
A6V10421795_en--_k
145 | 151
Outputs parameters of I/O modules
Devices
Output Mode
Fail safe
Output style
FDCIO221
Inactive: Off / Active: On
Freeze
Monitored output
FDCIO222
Inactive: Off / Active: On
Freeze
-
FDCIO224
Inactive: Off / Active: On
Freeze
-
FDCIO361
Inactive: Off / Active: On
Freeze
Monitored output
The default settings of 'Not in use' is 'No' for all the devices above.
Alarm device parameters
Devices
Volume
Beacon Intensity
Silent sounder
FDS224
High
-
-
FDSx226
High
Low
-
FDS225
High
-
-
FDSx227
High
Low
-
FDS364
-
-
-
FDS366
-
Medium
-
FT2010 floor repeater parameters
Items
Default settings
1
1. List faults
No
2. Not used
No
3. List isolations
No
4. List technical messages
No
5. Activate/deactivate sounders
No
6. Isolate RT fire
No
1
By default, both function keys and LEDs are disabled. Change the default
settings to Yes to enable function keys and LEDs.