3BPlanning
25BParameter sets: Neural fire detector
4
63 |
138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
Only select this parameter set if high sensitivity is required and no deceptive
phenomena (visible aerosols) can be expected.
No.
Name
Response time [s]
Sensitivity
To open fire/smoldering fire
[%/m]
0
1
Universal 50 2.3 / 8.0
2 Robust 80 2.3 / 8.0
1 Universal 50 2.3 / 8.0
3
2
Sensitive 30 1.6 / 5.6
4
3
Universal Fast 8 2.3 / 8.0
5 Super Sensitive 12 1.0 / 1.5
6 Ultra Sensitive 12 0.35 / 0.5
1
Delivery status; can only be selected in collective mode and MS8 mode.
2
Default status in AnalogPLUS mode as DO1131A
3
Can only be selected in AnalogPLUS mode
Parameter sets 0…5 meet the criteria of standard EN 54-7.
Parameter set 5 meets the criteria of standard EN 54-27. You will find more
information in documents A6V10446712 and A6V10427924. See 'Applicable
documents [➙ 9]' chapter.