P/N 315-034850-8
INTRODUCTION The Model HZM from Siemens Industry, Inc. is an intelligent device that connects a
single zone of conventional devices to a DLC (FireFinder-XLS System) or FS-DLC (FS-
250 System) device loop. The HZM can power up to fifteen compatible 2-wire, ioniza-
tion or photoelectric smoke detectors or it can power one PB-1191 Beam Detector. It
can also monitor an unlimited number of shorting devices such as waterflow switches,
thermal detectors, manual stations, etc.
Each HZM can be assigned a custom message using either the Zeus Programming
Tool (FireFinder-XLS System) or the FS-CT2 (FS-250 System). Refer to the Zeus Quick
Start Manual, P/N 315-033875, or the FS-250 Programming Manual, P/N 315-049403,
as applicable. The alarm verification configuration is used only for non-shorting detectors.
The HZM supports Class A and Class B wiring. The module uses one address on the
device loop. It does not require any mechanical address programming. Use the DPU
Device Programming Unit to program and test the module.
HZM HZM
FRONT BACK SIDE
ALARM
1 2 3 4
5
6 7 8 9
PROGRAMMING
POINTS
Figure 1
HZM Module
The HZM is not listed for use in mass notification applications.
Controls And Indicators The HZM has a multicolor LED, visable through the cover plate, which indicates the
condition of the circuit. This multicolor LED displays red for alarm, yellow for trouble,
and green for normal operation (See Figure 1).
PRE-INSTALLATION Setting The Module Address
1. Using the DPU Device Programming Unit, plug the programming cable into
the programming points on the HZM (See Figure 1).
2. Set the address for the HZM by following the instructions in the DPU
Manual, P/N 315-033260.
Remote Conventional Zone Module
Installation Instructions
Model HZM
Question and Answer IconNeed help?

Do you have a question about the Siemens HZM and is the answer not in the manual?

Siemens HZM Specifications

General IconGeneral
BrandSiemens
ModelHZM
CategoryControl Unit
LanguageEnglish

Summary

Introduction to Model HZM

Controls and Indicators

Pre-Installation Steps

Setting The Module Address

Procedure to set the HZM module address using the DPU Device Programming Unit.

Installation Guide

Electrical Connections

Details on connecting field wiring for initiating devices, device loop, and 24 VDC power.

Initiating Devices Wiring

Wiring diagrams for connecting initiating devices in Class A or Class B configurations.

Device Loops Configuration

HZM Device Loop Wiring Diagram For FireFinder-XLS

Diagrams showing Class A and Class B wiring for the HZM on the FireFinder-XLS DLC loop.

HZM Device Loop Wiring Diagram For FS-250

Diagrams showing Class A and Class B wiring for the HZM on the FS-250 FS-DLC loop.

24 VDC Power Connection

Mounting Instructions

Instructions for mounting the HZM module in a standard electrical box and securing it.

Electrical Ratings Summary