Building Technologies Division CC1N7550en
Industry Sector 24.05.2011
Technical data (cont’d)
For intermittent operation only.
&
Note!
AGQ1… is only available for AC 230 V mains voltage.
Power supply in operation DC 280…325 V
Power supply in test mode DC 390…750 V
For more detailed information about QRA2… / QRA10…, refer to Data Sheet N7712.
For more detailed information about QRA4.U, refer to Data Sheet N7711.
Caution!
QRA2… (QRA4.U / QRA10... must not be used when extraneous light suppres-
sion is activated since detector tests will not be made in that case!
Possible ionization current Max. 10 µA
Ionization current required Min. 6 µA
In connection with the LMV5…, ancillary unit AGQ1…A27 must be used.
Power supply AC 230 V
Possible current Max. 500 µA
Current required Min. 200 µA
7550a20/0308
br
bl
rt
sw
AGQ1...A27
sw
bl
QRA
X10-02 / 3
X10-02 / 4
X3-01 / 1
X10-03 / 1
LMV5...
Assignment of LMV5…terminals:
X10-02 / 3 L
X10-02 / 4 N
X10-03 / 1 Ionization
X3-01 / 1 Fan
When laid together with other cables (e.g. in a cable duct), the length of the 2-core ca-
ble between QRA… and AGQ… must not exceed 20 m. A maximum cable length of
100 m is permitted if the 2-core cable is run at a distance of at least 5 cm from other
live cables. The length of the 4-core cable between AGQ… and LMV5… is limited to
20 m. A maximum cable length of 100 m is permitted if the signal line (ionization /
black) is not run in the same cable but separately at a distance of at least 5 cm from
other live cables.
Flame supervision
QRA2… / QRA4.U /
QRA10… with
AGQ1…A27
QRA…
LMV5…
AGQ1…A27
Connection diagram