19/39
Building Technologies Division CC1N7550en
Industry Sector 24.05.2011
AGG5.631 (cable type 2)
AGG5.641 (cable type 1)
1 x SQM9...
1 x SQM48... + 1 x SQM9...
3
1 x SQM45... + 1 x SQM9...
CAN bus connection between power transformer and actuator group
&
Note!
When using a PLL52..., the maximum permissible cable length is to be reduced by
2 m.
Example:
- System cable: AGG5.641 (connecting cable to the actuators)
- Actuators: 2 x SQM45...
The point of intersection of the vertical line for the AGG5.641 (1.25 mm
2
) and curve d
(2 x SQM45...) gives a maximum cable length of 33.4 m between the power trans-
former and the group of actuators.
Diagram for cable
length SQM45...,
SQM48... and SQM9...