15/28 
Building Technologies Division    CC1N7785en 
  20.11.2017 
Function 
In contrast to conventional amplifiers, the signal delivered by the flame detector is 
handled dynamically and not statically. The flame detector signal is converted to a 
sequence of control pulses and then fed to the flame relay circuit. The latter is designed 
such that the flame relay can only be energized by a flame signal of the described form. 
If the pulses change due to a faulty detector or faulty detector cables, the relay will be 
deenergized and the burner control triggers the required safety actions. In the case of 
UV supervision, it must also be ensured that self-ignition of the UV tube (e.g. due to 
aging) does not simulate a flame signal. For that reason, incident radiation at the UV 
cell is periodically interrupted by a shutter. In addition to the self-checking facility, the 
flame signal circuit is subjected to a functional test during the prepurge time. If it does 
not operate correctly, the startup sequence will be aborted or lockout initiated. 
Furthermore, if mains voltage drops to a level where safe operation of the burner 
control is no longer ensured, the burner will automatically shut down. When mains 
voltage returns to the normal level, the burner control repeats the startup sequence. If 
the detector signals are only slightly above the minimum levels, such mains voltage 
fluctuations can also give rise to burner lockout however. 
 
-  The burner control is reset and in the start position (terminals 11 and 12 must 
receive power) 
-  The air damper is closed. The end switch (z) for the CLOSED position must pass 
voltage from terminal 11 to terminal 8 
-  All control contacts between terminals 12 and 5 (limit thermostat, control 
thermostat, etc.) must be closed 
Principle of  
self-supervision 
Prerequisites for  
burner startup