MICROMASTER Vector 6SE32
MIDIMASTER Vector 6SE32
Getting Started
Caution: Before installing and
putting this equipment into
operation, please read the 
Operating Instructions Manual for
Safety Precautions and Warnings
SIEMENS MICROMASTER
Step 1    Connecting up the MMV and MDV
230V Single Phase                     400V Three Phase
The MICROMASTER Vector (MMV) and the 
MIDIMASTER Vector (MDV) are a range of frequency 
inverters for controlling the speed of three phase AC 
induction motors.
Note: Motors above 11kW are usually configured 
400V Delta / 690V Star.  
In this case the motor should be connected in Delta.
Star connection for 
400V 3 phase
Delta connection for 
230V 3 phase
MIDIMASTER Vector (MDV)
The MDV electrical installation section of the 
Operator Instructions Manual shows the position of 
the terminals used to connect the power and the 
motor.
At any time, press the 'STOP' button and watch the 
motor stop.
Step 3     Changing the speed of the motor
The default output frequency of the drive is 5Hz (see 
Hints and Tips to convert this to RPM). This speed will 
probably be too low for most applications and a speed 
change may be required. The following steps will allow 
you to change the preset value of the inverter output to 
the required speed.
Step / Action
Press the 'P' button to access the parameter settings.
P000
P005
005.0
035.0
P005
P000
000.0
035.0
Press the  button 5  times until  the display  reads P005.
Display
Press the 'P' button to display the current parameter value.
Press the       button to change the value to 35Hz. (This 
number can be any number between 0 and 50Hz - default.)
Press the 'P' button to store the new value.
Press the  button until the display reads P000.
Press the 'P' button to exit the parameterisation procedure.  
The display will alternate between the output frequency and 
the frequency set point.
The required speed has now been stored. 
This method is used to access all parameters.
The drive can now be started by pressing the 'RUN' 
button. It will ramp up to the frequency held in parameter
P005 and remain there. To stop the drive press the 
'STOP' button, the drive will then ramp down to 0Hz 
output. 
Default Parameters:
Digital input
ParameterTerminal Default
1
2
3
4
5
6
5
6
7
8
16
17
P051 = 1
P052 = 2
P053 = 6
P054 = 6
P055 = 6
P356 = 6
ON right
ON left
Fixed frequency 3
Fixed frequency 2
Fixed frequency 1
Fixed frequency 6
Output
Relays 
1
2
18/19/20
21/22
P061 = 6
P062 = 8
Fault identification
Warning active
Fault Codes:
Motor overtemperature by I²t 
calculation
Other faults, see manual
F001
F002
F003
F005
F074
Overvoltage
Overcurrent
Overload
Inverter overtemperature 
(internal PTC)
http://www.con.siemens.co.uk
For further Technical Support 
Information, and to submit your 
suggestions for improvements, 
see our Web Site:
Siemens plc
Automation and Drives
Varey Road
Congleton
Cheshire CW12 1PH
Great Britain
May 1999 
English
Order Number: 6SE3286-4BA86 
G85139-H1751-U568-D1
F004           Overheating  of  motor  (PTC)
This is the
STOP button''
STOP''
'DOWN' button
Hz