Configuring NK8000
45
Building Technologies 048_DMS_NK8000_ICC_MP4.40_A6V10062437_a_en.doc
Fire Safety & Security Products 06.2011
8.2 Configuring NK82xx IP – via NW8202
This configuration must be performed before the NK82xx(s) can be configured at
the client’s site. This procedure details how to send the IP configuration informa-
tion; that is, the IP address, Subnet mask, and Default address to the NK82xx via
the NW8202 Tool.
Note: This configuration procedure can be performed prior to shipping the NK82xx
to the client, or at a later time at the client’s site.
1. Set the Service PC IP address to 192.168.9.1 and the subnet mask to
255.255.255.0.
a) Select Start Settings Network and Dial Up Connections
b) Double-click Local Area Connection
c) Click the Properties button
d) Select Internet Protocol (TCP/IP)
e) Click the Properties button
f) Make note of the current IP address before replacing it with the new one
2. Click OK to restart PC when prompted.
3. Remove the cover of the NK82xx to be configured
(press the 4 white tabs to the rear of the left and right sides of the unit and lift
gently)
4. Open the NW8202 application by selecting NW8202.exe located in
<InstallDir>\Utilities\NW8202 folder
5. Select the Firmware Version
Note: if NK823x is not indicated with a specific option, use latest NK822x.
6. Enter IP address, Subnet mask, and Default gateway in the corresponding
fields (Fig. 30)
Fig. 30 NW8202 IP configuration download tool
7. Click Download
The Download Procedure window is displayed. (Fig. 31)
8.
Follow the instructions displayed.