Maintenance and diagnostics
55
Building Technologies 048_DMS_NK8000_ICC_MP4.40_A6V10062437_a_en.doc
Fire Safety & Security Products 06.2011
10.3.4 Uploading diagnostic files
Diagnostic file purposes:
The purpose of these files is to record messages of what has taken place with the
NK82xx to make it easier to determine if something is wrong, or if something im-
portant has taken place.
Diagnostic file descriptions:
DIAGNO.LOG – This file is always present, and contains information about the be-
haviour of the application running on the NK82xx. For example, if it wasn’t possible
to open an internal queue during the initialisation phase, that message is saved to
this file.
EEProm.LOG – You create this file by selecting the Save EEProm on File button.
This file contains information about the NK82xx hardware status stored on the
EEProm. For example, if it wasn’t possible to use the serial interface on COM3 be-
cause the serial add-on board is broken, that message is saved to the EEProm.
Note: Every time you select the Save EEProm on File button, you overwrite any
existing EEProm.LOG file.
EVENT.LOG – This file is present only after the EEProm is full for the first time. It
contains (up to) the four most recent backups of the EEProm.LOG file.
A detailed description of the EEProm log entries is provided in the table here be-
low.
ID Message text Meaning
0 EV_EEPROM_NULL -
1 EV_EEPROM_INIT EEProm initialization
2 EV_EEPROM_START NK8000 unit restart
3 EV_EEPROM_NOT_ALIGNED EEProm not aligned
4 EV_EEPROM_NO_ETH_INIT Ethernet initialization failed
5 EV_EEPROM_TAMPER_OPEN NK8000 unit box opened
6 EV_EEPROM_TAMPER_CLOSE NK8000 unit box closed
8 EV_EEPROM_NO_SER0_INIT COM1 initialization failed
9 EV_EEPROM_NO_SER1_INIT COM2 initialization failed
10 EV_EEPROM_NO_SER2_INIT COM3 initialization failed
11 EV_EEPROM_NO_SER3_INIT COM4 initialization failed
12 EV_EEPROM_SER0_ERROR COM1 error
13 EV_EEPROM_SER1_ERROR COM2 error
14 EV_EEPROM_SER2_ERROR COM3 error
15 EV_EEPROM_SER3_ERROR COM4 error
16 EV_EEPROM_DATE_TIME Date and time changed within delta threshold
17 EV_EEPROM_NEW_DATE_TIME Date and time changed over delta threshold
18 EV_EEPROM_RESET Reset command
19 EV_EEPROM_EMERGENCY Restart in emergency mode
20 EV_EEPROM_FTP_SESSION FTP session opened
21 EV_EEPROM_CONFIG_CHANGE Configuration file changed
22 EV_EEPROM_SW_CHANGE Software version changed
23 EV_EEPROM_CPU_CHANGE CPU changed
24 EV_EEPROM_ETH_PNP_UPDATE Ethernet EEProm update
25 EV_EEPROM_ETH_PNP_ERROR Ethernet EEProm update failed
34 EV_EEPROM_DLL_LOAD_FAILED DLL load failure
35 EV_EEPROM_DLL_EXCLUDED DLL excluded from round-robin schedule
36 EV_EEPROM_DLL_OVERRUN DLL response time over threshold 1
37 EV_EEPROM_DLL_VER_ERR DLL version error
38 EV_EEPROM_DLL_INIT_ERR DLL initialization error
39 EV_EEPROM_DLL_OVERTIME DLL response time over threshold 2
40 EV_EEPROM_DLL_TIMEOUT DLL response time over threshold 3
41 EV_EEPROM_DLL_EVENT DLL diagnostic event
42 EV_EEPROM_HW_MISMATCH
PIC24 microcontroller init detected a hardware