System limits
NK823x system limits
3
17
Building Technologies
A6V10062437_a_en
Fire Safety & Security Products 30.06.2013
Interaction capabilities
NK8232 and NK8235 provides programmable interaction programs, including single or
multiple triggers (incoming events) and single or multiple effects (outgoing control
actions). Interactions are only possible between locally connected subsystems.
For supported subsystems see Interactions [➙ 12]
Logical combinations: AND, OR, XOR, NOT
Delay of effects (wait): configurable 0…6500 sec
Max. # of typical interactions (1-6 triggers, 1-4 effects): 500
Total # of field points used in triggers/effects: 5000
Max. # of field points/interactions that can be combined in a trigger expression: 255
Modules locally connected via I
2
C
Up to 4 DF80xx modules in total
1 DF8090 Power supply supervision module
Up to 4 DF8020 relay output modules
Up to 4 DF8040 non supervised inputs modules
Up to 4 DF8045 supervised NC input modules
Up to 4 DF8046 supervised NO input modules
Note: Locally connected DF8000 I/O modules are only supported with NK823x with
build state 10 or higher (NKM8001-A2 mainboard; check the last two digits after the
part no. on the NK823x type label).