Structure and functions
NK822x hardware
4
23
Building Technologies
A6V10062437_a_en
Fire Safety & Security Products 30.06.2013
The logical BACnet address of NK822x is fixed to 1. This address has to be con-
figured in the CS6 Guarto using the tool SWE6 for Guarto MP3 (Node CerCom Bus,
properties of node Management Station).
Note: The physical LON addresses and the logical BACnet addresses must be unique
in a LON-network.
Guarto MP2b is no longer supported in NK8000 MP3.15 and higher.
4.1.6 Ethernet interface
The NK822x main board is equipped with one Ethernet interface and an RJ-45
connector. A green LED (internal) flashes when data is received or transmitted.
Back
Ethernet connector on NK822x
4.1.7 I2C interface: I/O and power supervision
This interface allows for a direct support of:
Direct digital input/output:
One or two DF8040 (CF9040) input modules
One DF8020 (CF9020) output module
Power supply supervision:
One DF8090 power supply supervision module
All modules can be installed on the DIN-rail, next to NK822x unit.
DF8020
DF8020 is a module providing 8 relay outputs, NO or NC.
DF8040
DF8040 is a module providing 8 inputs, which can be normally open or normally closed
and driven by dry contacts or open collector signals
See NK822x hardware installation [➙ 37] for more information on the c
onnection of I/O
modules to the NK822x