Mounting and installation
2
31
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
NOTICE
The test is made to check the quality of the radio link.
Testing takes place at the final installation location.
1. Press the button on the RF repeater from 3 to (at most) 8 seconds.
a The LED blinks slowly.
- When radio communications are operating correctly, the LED on the RF
module (AVS71.390) flashes briefly at 10-second intervals.
- With RF module BSB (AVS71.393), the LEDs go off every 10 seconds.
2. After the test, press the button on the RF repeater again briefly until the LED
extinguishes.
The test can be cancelled by pressing the ESC button.
The RF repeater forwards the RF signals between RF module (BSB) and base unit.
No further binding between the RF repeater and room unit required.
Testing
Operating principle