NOTICE
The test is made to check the quality of the radio link.
Testing takes place at the final installation location.
1. Press the occupancy button for at least 3 seconds.
a The room unit switches to the service level (Display "ru..").
2. Press occupancy button 4 times, until "P4" appears.
3. Press operating mode button.
a Test mode begins. 24 telegrams are sent.
The test can be stopped by pressing the operating mode or occupancy but
tons.
Example of a display during the test:
The test results are displayed on the display:
l The digits on the left show telegrams that have been sent, the digits on the
right telegrams that have been received.
l The test will be ended after 24 telegrams. The test is considered successful
when at least 50% of the telegrams sent have been received.
l If the test was not successful, some other mounting location should be chosen,
or the AVS14.390 RF repeater should be used.