EasyManua.ls Logo

Siemens QRI2B2.B180B1 - Technical Detector Specifications; General Detector Data Sheet; Environmental Operating Conditions

Siemens QRI2B2.B180B1
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6/12
Building Technologies CC1N7719en
17.07.2018
Technical data
Operating voltage
- Operation
- Test
DC 14 V ±5%
DC 21 V ±5%
Signal voltage DC 0...5 V
Length of connecting cable Max. 180 cm
Degree of protection IP54
Power consumption <0.5 W
Length of auxiliary detector cable Max. 100 m
Safety class II
Vibrations to IEC 6068-2-6 Max. 1 g / 10...500 Hz
Weight incl. cable 180 cm Approx. 0.175 kg
Mounting position Optional
Storage DIN EN 60721-3-1
Climatic conditions Class 1K3
Mechanical conditions Class 1M2
Temperature range -20...+60 °C
Humidity <95% r.h.
Transport DIN EN 60721-3-2
Climatic conditions Class 2K2
Mechanical conditions Class 2M2
Temperature range -20...+60 °C
Humidity <95% r.h.
Operation DIN EN 60721-3-3
Climatic conditions Class 3K5
Mechanical conditions Class 3M2
Temperature range -20...+60 °C
short-time (max. 1 min) up to 75 °C
Humidity <95% r.h.
Installation altitude Max. 2,000 m above sea level
Attention!
Condensation, formation of ice and ingress of water are not permitted!
If not observed, the safety functions are no longer ensured and there will be a
risk of electric shock.