8/12
Siem ens Room temperature controllers CE1N3072en
Building Technologies 2014-04-04
Technical data
Operating voltage DC 3 V (2 x 1.5 V AA alkaline batteries)
Battery life >1 year (AA alkaline batteries)
Thermistor 10 kΩ ± 1% at 25 °C
Switching differential SD 1 K (fixed)
Setpoint setting range 5…30 °C (Comfort mode)
5…30 °C (Energy Saving mode)
5 °C (Frost Protection, fixed value)
Factory setting comfort setpoint 20 °C
Factory setting for energy saving mode 10 °C
Resolution of settings and displays
Setpoints 0.5 °C
Actual value displays 0.5 °C
Display of time of day 1 min
Operation IEC 60721-3-3
Climatic conditions Class 3K5
Temperature 0…+40 °C
Humidity <90% r.h.
Transport IEC 60721-3-2
Climatic conditions Class 2K3
Temperature -25…+60 °C
Humidity <95 % r. h.
Mechanical conditions Class 2M2
Storage IEC 60721-3-1
Climatic conditions Class 1K3
Temperature -10…+60 °C
Humidity <90% r.h.
EU Conformity (CE) CE1T10886xx
*)
C-tick conformity to
Test standards and requirements EN 61000-6-3, AS/NZS 4251.1
Test standards for radio equipment AS/NZS 4268
Safety class III as per EN 60950-1
Pollution degree 2
Degree of protection of housing IP20
Weight (including package)
RDJ10RF/SET 515 g
Color of housing front Signal-white RAL9003
Housing material ABS (LCD lens: PC)
Power supply
Operational data
Environmental conditions
Standards
General