Siemens RDF302 Basic documentation CE1P3079en
Smart Infrastructure 2022-06-17
The current setpoint (used by the thermostat for temperature control) is available
on the Modbus for use in the central control unit.
Changes via the local HMI or via tool have the same priority (last always wins)
Setting the Comfort basic setpoint will reset the runtime Comfort setpoint to the
basic setpoint
The resulting (current) setpoint heating and cooling is limited by the Protection
setpoint; if Protection setpoint is OFF, then minimum 5 °C and maximum 40 °C
are used
The resulting setpoints for cooling and heating of the same operating mode have
a minimum distance of 0.5 K between them
Room temperature:
Current setpoint
General notes:
Notes on setpoint
adjustment