Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
VI_RFLT1.PhV
Information Value
Va (Va =) VI_RFLT1.PhV.phsA.cVal.mag.f Measured Value Value
VI_RFLT1.PhV.phsA.units.SIunit 29 V
VI_RFLT1.PhV.phsA.units.multiplier 0 1
Information Value
Vb (Vb =) VI_RFLT1.PhV.phsB.cVal.mag.f Measured Value Value
VI_RFLT1.PhV.phsB.units.SIunit 29 V
VI_RFLT1.PhV.phsB.units.multiplier 0 1
Information Value
Vc (Vc =) VI_RFLT1.PhV.phsC.cVal.mag.f Measured Value Value
VI_RFLT1.PhV.phsC.units.SIunit 29 V
VI_RFLT1.PhV.phsC.units.multiplier 0 1
VI_RFLT1.A
Information
Value
Ia (Ia =) VI_RFLT1.A.phsA.cVal.mag.f Measured Value Value
VI_RFLT1.A.phsA.units.SIunit 5 A
VI_RFLT1.A.phsA.units.multiplier 0 1
Information Value
Ib (Ib =) VI_RFLT1.A.phsB.cVal.mag.f Measured Value Value
VI_RFLT1.A.phsB.units.SIunit 5 A
VI_RFLT1.A.phsB.units.multiplier 0 1
Information Value
Ic (Ic =) VI_RFLT1.A.phsC.cVal.mag.f Measured Value Value
VI_RFLT1.A.phsC.units.SIunit 5 A
VI_RFLT1.A.phsC.units.multiplier 0 1
Information Value
Ineut (Ig =) VI_RFLT1.A.neut.cVal.mag.f Measured Value Value
VI_RFLT1.A.neut.units.SIunit 5 A
VI_RFLT1.A.neut.units.multiplier 0 1
IEC 61850 Functional Information Mapping – Last Trip Current (I_RFLT)
I_RFLT.Mod
Information
Reset Device x
Device Functionality
3.6 Data Storage
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 117
C53000-G7040-C014-1, Edition 11.2019