60CTS‑V CT Supervision – Voltage Reference
Reference
Parameter Value
I
set
I2 setting 0.05 to 1, Δ 0.05
V
set
V2 setting 7 to 110 V, Δ 1 V
t
delay
Delay setting 0.03 to 20 s, Δ 0.01 s
20 to 100 s, Δ 0.1 s
100 to 1000 s, Δ 1 s
1000 to 10000 s, Δ 10 s
1000 to 14400 s, Δ 100 s
Operate and Reset Time
Attribute Value
t
basic
Element basic operate time 30 ms ± 20 ms
t
op
Operate time following delay t
basic
+ t
delay
± 1 % or ± 20 ms
Repeatability ± 1 % or ± 20 ms
10.27
Technical Data
10.27 60CTS‑V CT Supervision – Voltage Reference
542 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019