Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value No-Dir: 0
FWD: 1
REV: 2
Information List
Input/Output Matrix General
Pickup
User Logic Type IEC
60870-5-1
03
DNP3 MODBUS
RTU
Inhibit 50N-n Inhibit 50N-n Input
50N-n
Pickup
50N-n Pickup Output
50N-n 50N-n Operated Output
E/F off/on Control Y Y Y
The complete serial protocol information list containing the DNP3, IEC 60870-5-103, and Modbus RTU data
information for the configured device can be generated using the Export Report feature in the Reydisp
Manager 2 tool, Serial Comms & Events.
5.15.7
Protection and Automation Functions
5.15 50N Instantaneous Earth Fault – Calculated
240 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019